(2000) Factors that Influence Transformer No-Load Current Harmonics. IEEE Transactions On Power Delivery, 15 (1). pp. 163-166.
Full text not available from this repository.Abstract
The harmonic components of the no-load current are influenced by many factors. These factors are the flux density, the degree of saturation and the core stacking technique. This paper tested many transformers for the no-load current and its harmonic components. A slight over-excitation results in a substantial increase of the THD level. The increase in the THD is not linear with the flux density. Also this work has demonstrated that having a lower no-load current should not be an indication of lower harmonics. The simulation of the transformer through the use of nonlinear inductors and resistors provided reasonable accuracy.