(1994) Induced voltages on fence wires and pipelines by AC powertransmission lines. Industry Applications, IEEE Transactions on, 30.
|
PDF
14827_1.pdf Download (18kB) | Preview |
|
Microsoft Word
14827_2.doc Download (26kB) |
Abstract
A method is developed for calculating the induced voltages on fence wires/pipelines underneath AC power transmission lines. The method is based on the charge simulation technique and takes into account the disturbances of the electric field and potential due to the presence of the fence wire/pipeline underneath the line. The calculated values of the induced voltage on fence wires are compared with those measured before. Induced voltages on pipelines underneath 230- and 380-kV lines are measured, correlated to the calculated values and discussed in the light of electric field induction on objects adjacent to AC power transmission lines
Item Type: | Article |
---|---|
Subjects: | Computer |
Department: | College of Engineering and Physics > Electrical Engineering |
Depositing User: | Mr. Admin Admin |
Date Deposited: | 24 Jun 2008 13:51 |
Last Modified: | 01 Nov 2019 14:07 |
URI: | http://eprints.kfupm.edu.sa/id/eprint/14827 |