Chaudhry, Muhammad Akhtar (1988) Generation outage dynamic contingency analysis using frequency prediction. Masters thesis, King Fahd University of Petroleum and Minerals.
| PDF 2758Kb |
Arabic Abstract
-
English Abstract
A more general average system frequency prediction formula has been proposed in this thesis. The frequency formula predicts the post disturbance minimum frequency and its time of occurrence following a major disturbance such as loss of a block of generating units or major tie lines. This closed form frequency formula is in terms of the power plant parameters, disturbance sizes, and load shedding relay set-points. It also predicts the time at which load is shed and real electrical and mechanical power of generators as a function of time. The results of frequency prediction formula have been compared with the average system frequency obtained by simulation. This frequency formula was incorporated in a fast decoupled load flow program to produce a dynamic load flow which was used to perform loss of generation / load contingency analysis. Two frequency performance indices have been proposed for comparison and ranking of critical contingencies. Several contingencies analysis were performed and these contingencies were ranked. A rate of change of frequency dependence load shedding scheme was designed and compared with one of the existing load shed schemes.
| Item Type: | Thesis (Masters) |
|---|---|
| Date: | June 1988 |
| Date Type: | Completion |
| Subjects: | Electrical |
| Divisions: | College Of Engineering Sciences > Electrical Engineering Dept |
| Creators: | Chaudhry, Muhammad Akhtar |
| Committee Advisor: | Somuah, Clement B. |
| Committee Members: | Abdurrahim, Abuhamed M. and Al-Shehri, Abdallah M. |
| ID Code: | 9820 |
| Deposited By: | KFUPM ePrints Admin |
| Deposited On: | 22 Jun 2008 16:49 |
| Last Modified: | 25 Apr 2011 09:30 |